Gas Chromatograph for Dissolved Gas Analysis in Transformer Oil
变压器油溶解气体分析气相色谱仪
- SKU TOT-0002
- Transformer Oil Testing
- CE (to be confirmed)
- ISO 9001 manufacturing (to be confirmed)
Price on request — FOB / CIF quoted per order
Prices depend on configuration, quantity and destination port.
Key specifications
| Gases measured | H2, O2, N2, CH4, CO, CO2, C2H4, C2H6, C2H2 |
|---|---|
| Detectors | TCD and FID with methanizer |
| Detection limit, hydrogen | ≤ 5 ppm (v/v in oil) |
| Detection limit, hydrocarbons | ≤ 1 ppm (v/v in oil) |
| Oil sample volume | ≈ 20–50 mL |
| Extraction method | Automated headspace or vacuum |
By Lab Manufacturers China Technical TeamLast reviewed Standards: IEC 60156, ASTM D1816, ASTM D877
What is the Gas Chromatograph for Dissolved Gas Analysis in Transformer Oil?
A dissolved gas analysis gas chromatograph separates and quantifies hydrogen, hydrocarbons and carbon oxides extracted from transformer oil. It is the main diagnostic tool for detecting partial discharge, overheating and arcing inside oil-filled equipment, and suits utilities and service laboratories with large transformer fleets.
What is the Gas Chromatograph for Dissolved Gas Analysis in Transformer Oil?
A dissolved gas analysis gas chromatograph separates and quantifies hydrogen, hydrocarbons and carbon oxides extracted from transformer oil. It is the main diagnostic tool for detecting partial discharge, overheating and arcing inside oil-filled equipment, and suits utilities and service laboratories with large transformer fleets.
Overview
The dedicated GC is configured for fault gases: a thermal conductivity detector for hydrogen, oxygen, nitrogen, carbon monoxide and carbon dioxide, and a flame ionization detector, often with a methanizer, for methane, ethane, ethylene, acetylene and carbon oxides at ppm level. Gases are extracted from oil by multistage vacuum extraction, mercury-free Toepler-type systems, or automated headspace equilibration, then injected through gas sampling valves onto packed or capillary columns. Detection limits are typically 1 to 5 ppm for hydrocarbons and 5 to 10 ppm for hydrogen in oil. Calibration with certified gas mixtures and repeatable extraction efficiency are essential. Results feed interpretation methods such as IEC 60599 ratios and the Duval triangle.
How does it work?
Insulating oil must resist electrical stress, remove heat and protect paper insulation, so testing targets each of these functions. Dielectric breakdown voltage is measured by increasing AC voltage at a fixed rate between standard electrodes in a stirred test cell until a discharge occurs. Dissolved gas analysis extracts gases from oil by headspace, vacuum or stripping and separates hydrogen, methane, ethane, ethylene, acetylene, carbon monoxide and carbon dioxide by gas chromatography with thermal conductivity and flame ionization detectors. Karl Fischer coulometry titrates water electrochemically. Dissipation factor and resistivity are measured in a three-terminal cell heated to 90 degrees Celsius. Interfacial tension uses a platinum ring that is pulled through the oil-water interface, and the pulling force gives the tension in mN/m.
What are the key features?
- Dual detector configuration with TCD and FID plus methanizer
- Automated headspace or vacuum extraction of oil samples
- Electronic pressure control for stable retention times
- Fault gas report templates for IEC 60599 and IEEE C57.104
- Autosampler for 12 to 40 oil samples
What are the technical specifications?
A typical gas chromatograph for dissolved gas analysis in transformer oil configuration offers gases measured of H2, O2, N2, CH4, CO, CO2, C2H4, C2H6, C2H2, detectors of TCD and FID with methanizer, detection limit, hydrogen of ≤ 5 ppm (v/v in oil), detection limit, hydrocarbons of ≤ 1 ppm (v/v in oil), oil sample volume of ≈ 20–50 mL and extraction method of Automated headspace or vacuum. Values are indicative of the product class; the exact figures for each configuration are confirmed on the quotation and the calibration documents supplied with the instrument.
Which applications is it used for?
The Gas Chromatograph for Dissolved Gas Analysis in Transformer Oil is used in utility laboratory fault monitoring, transformer manufacturer factory tests and independent DGA service laboratories. Across the wider Transformer Oil Testing class, laboratories also deploy it for transformer acceptance and commissioning tests, routine insulating oil monitoring for utilities and fault diagnosis by dissolved gas analysis.
Which standards and certifications apply?
Relevant standards and methods include IEC 60156, ASTM D1816, ASTM D877, IEC 60599, ASTM D3612, IEC 60814, IEC 60247, ASTM D971 and GB/T 507. Certification candidates for this model are CE and ISO 9001 manufacturing; each is to be confirmed for the specific configuration before shipment, and certificates are supplied only where they have been issued.
Sampling is as critical as analysis: use clean, dry glass syringes or sampling bottles, avoid air exposure for dissolved gas samples and record oil temperature. Test cells and electrodes must be cleaned and rinsed with the test oil, and gap distance verified with a gauge. High-voltage testers need grounded benches, interlocked lids and periodic verification of voltage and rate of rise. Gas chromatographs require carrier gas purity, column conditioning and calibration with certified gas mixtures. Karl Fischer reagents are replaced per usage. Follow facility safety rules, and dispose of oil and halogenated waste according to regulations.
How do I select the right Gas Chromatograph for Dissolved Gas Analysis in Transformer Oil?
Select a DGA gas chromatograph when your organization manages many transformers and needs diagnostic capability, not just screening. Specify gas list, extraction method (headspace or vacuum), detector set, carrier and hydrogen supply, sample capacity and reporting to IEC 60599 or IEEE C57.104 for fault interpretation.
How does it compare with other Transformer Oil Testing variants?
Choose equipment by the decisions it supports. A breakdown voltage tester is the minimum for acceptance and routine screening; select the test voltage class (80 kV for most service oil, 100 kV or higher for new oil and EHV equipment) and the electrode type that your standard requires, VDE or spherical for IEC 60156, or ASTM D1816 or D877 types. Dissolved gas analysis is the key diagnostic for fault detection and suits utilities with many assets. Coulometric Karl Fischer is needed because moisture strongly affects paper insulation life. Tan delta and resistivity testers help detect polar contaminants and aging, while IFT indicates sludge precursors. Also check sample volume, automation level, test-cell cleaning, data logging and safe high-voltage interlocks.
Full specifications
| Gases measured | H2, O2, N2, CH4, CO, CO2, C2H4, C2H6, C2H2 |
|---|---|
| Detectors | TCD and FID with methanizer |
| Detection limit, hydrogen | ≤ 5 ppm (v/v in oil) |
| Detection limit, hydrocarbons | ≤ 1 ppm (v/v in oil) |
| Oil sample volume | ≈ 20–50 mL |
| Extraction method | Automated headspace or vacuum |
| Analysis time | ≈ 12–20 min per sample |
| Repeatability (RSD) | ≤ 3 % |
| Oven temperature range | Ambient +5 to 400 °C |
Indicative values for this product class. Final specifications are confirmed on the quotation and in the calibration documents supplied with the instrument.
Applications
- Utility laboratory fault monitoring
- Transformer manufacturer factory tests
- Independent DGA service laboratories
Key features
- Dual detector configuration with TCD and FID plus methanizer
- Automated headspace or vacuum extraction of oil samples
- Electronic pressure control for stable retention times
- Fault gas report templates for IEC 60599 and IEEE C57.104
- Autosampler for 12 to 40 oil samples
Frequently asked questions about Gas Chromatograph for Dissolved Gas Analysis in Transformer Oil
Standard DGA measures hydrogen, methane, ethane, ethylene, acetylene, carbon monoxide and carbon dioxide, plus oxygen and nitrogen. Hydrogen indicates partial discharge, acetylene indicates arcing, and ethylene and methane point to thermal faults in oil.
Headspace extraction is easier to automate and avoids mercury, while vacuum extraction gives higher recovery for heavier gases. Both are acceptable in ASTM D3612 and IEC 60567 when validated, and extraction efficiency should be verified with reference oils.
Routine annual DGA detects slowly developing faults. A sudden gas-rate increase between samples signals acceleration and should trigger resampling within days. Continuous online monitors complement laboratory DGA by tracking key gases in near real time.
Standard tests include dielectric breakdown voltage, water content, acidity, dissipation factor, resistivity, interfacial tension and dissolved gas analysis. Together they assess insulating strength, contamination, aging and incipient faults, with frequency depending on transformer voltage class and criticality.
Dissolved gas analysis extracts gases from transformer oil and measures hydrogen, hydrocarbons and carbon oxides by gas chromatography. Gas ratios and concentrations indicate fault types such as partial discharge, overheating or arcing, using interpretation methods in IEC 60599 or IEEE C57.104.
Water lowers dielectric strength and accelerates cellulose degradation, shortening transformer life. Because most water resides in the paper insulation, oil moisture is interpreted together with temperature, using equilibrium curves to estimate paper moisture content.
Related models



Dielectric Loss Tangent and Volume Resistivity Tester for Insulating Oil
绝缘油介质损耗及体积电阻率测试仪
- CE (to be confirmed)
- +1