Floor-Mounted Drench Shower
落地式喷淋淋浴
- SKU ESH-0002
- Emergency Showers
- CE (to be confirmed)
- ISO 9001 manufacturing (to be confirmed)
Price on request — FOB / CIF quoted per order
Prices depend on configuration, quantity and destination port.
Key specifications
| Type | Floor-mounted drench shower |
|---|---|
| Shower flow | 75–115 L/min |
| Water temperature | 16–38 °C tepid |
| Head height | 2000–2400 mm |
| Spray diameter | 500–900 mm |
| Supply pressure | 1.5–3.0 bar |
By Lab Manufacturers China Technical TeamLast reviewed Standards: ANSI/ISEA Z358.1 (emergency eyewash and shower equipment), EN 15154-1 (body showers for laboratories), EN 15154-2 (eyewash)
What is the Floor-Mounted Drench Shower?
A floor-mounted drench shower is a standalone column with an overhead head for whole-body flushing. It is installed where a dedicated body shower is required without eyewash and a separate eyewash is nearby.
What is the Floor-Mounted Drench Shower?
A floor-mounted drench shower is a standalone column with an overhead head for whole-body flushing. It is installed where a dedicated body shower is required without eyewash and a separate eyewash is nearby.
Overview
The unit is a floor-standing column, 2000–2400 mm high, with a large overhead head and a stay-open valve operated by a pull rod or chain. It delivers 75–115 L/min of tepid water over the body so that chemicals are diluted and washed away, and the spray covers a diameter of 500–900 mm at standing height. The column is galvanised or stainless steel, and the base is bolted to the floor for stability. A floor drain and a clear approach are required, and the unit should be within 10 seconds of the hazard. Because there is no eyewash, it is used in areas where eye exposure is not expected, such as bulk chemical handling, or where a separate eyewash is provided nearby. Weekly activation and annual inspection keep it reliable.
How does it work?
An emergency shower is a fixed deluge device that floods the user with water at a controlled rate, temperature and pattern so that chemicals are diluted and washed from skin, hair and clothing. Water comes from a dedicated supply through a stay-open valve, so once the user pulls the handle both hands are free. The shower head distributes the flow over the body, and the column height and spray diameter are specified so a standing person is fully covered. Flow is typically 75–115 L/min at a pressure of 1.5–3.0 bar, and water should be tepid, roughly 16–38 °C, because cold water can prevent a casualty from staying under the shower long enough. A floor drain and a clear area around the unit are part of the installation, and combination units add eyewash heads at working height.
What are the key features?
- Floor-mounted column, 2000–2400 mm high
- Overhead head covering 500–900 mm
- Flow 75–115 L/min, stay-open valve
- Pull rod or chain activation
- Galvanised or stainless steel
- Bolted base for stability
What are the technical specifications?
A typical floor-mounted drench shower configuration offers type of Floor-mounted drench shower, shower flow of 75–115 L/min, water temperature of 16–38 °C tepid, head height of 2000–2400 mm, spray diameter of 500–900 mm and supply pressure of 1.5–3.0 bar. Values are indicative of the product class; the exact figures for each configuration are confirmed on the quotation and the calibration documents supplied with the instrument.
Which applications is it used for?
The Floor-Mounted Drench Shower is used in bulk chemical handling, process and plant areas, solvent transfer points and industrial laboratories. Across the wider Emergency Showers class, laboratories also deploy it for chemical laboratories, battery and plating areas and pharmaceutical and QC laboratories.
Which standards and certifications apply?
Relevant standards and methods include ANSI/ISEA Z358.1 (emergency eyewash and shower equipment), EN 15154-1 (body showers for laboratories), EN 15154-2 (eyewash), DIN 12899 (emergency safety showers), ISO 3864 (safety signage) and GB/T 38144 (emergency shower and eyewash). Certification candidates for this model are CE and ISO 9001 manufacturing; each is to be confirmed for the specific configuration before shipment, and certificates are supplied only where they have been issued.
Activate every shower weekly to flush stagnant water and verify that the valve opens fully and stays open, and inspect annually for flow, temperature, spray pattern and height against ANSI/ISEA Z358.1 or EN 15154. Keep the approach clear of stored equipment, since an obstructed shower cannot be used in an emergency. Maintain tepid water within the required range, and check the mixing valve or heater regularly. Provide a floor drain or containment so contaminated water does not spread, and confirm the unit is not used for any other purpose. Record weekly and annual checks, and train staff on locations and on flushing for at least 15 minutes before seeking medical help.
How do I select the right Floor-Mounted Drench Shower?
Choose a floor-mounted drench shower where whole-body flushing is needed without eyewash, provided a separate eyewash is within 10 seconds if eye exposure is possible. RFQ: hazards, head height, flow, supply and drain. Confirm the unit is clearly signposted.
How does it compare with other Emergency Showers variants?
Choose the type by the hazard and the room. A floor-mounted drench shower suits general laboratories, while a wall-mounted unit saves floor space where the wall is rated for the load. A combination shower and eyewash covers whole-body and eye exposure in one unit, which is often the most efficient layout. Add a tempered water supply where the incoming water is too cold, since cold water discourages full 15-minute flushing. For strong corrosives, heat-sensitive chemicals or large spill risks, an enclosed booth with a curtain or drainage keeps contaminated water contained. Confirm access within 10 seconds' travel of hazards, on the same level, unobstructed, and verify flow, temperature and spray coverage at commissioning. Provide signage and a floor drain.
Full specifications
| Type | Floor-mounted drench shower |
|---|---|
| Shower flow | 75–115 L/min |
| Water temperature | 16–38 °C tepid |
| Head height | 2000–2400 mm |
| Spray diameter | 500–900 mm |
| Supply pressure | 1.5–3.0 bar |
| Valve type | Stay-open, pull rod |
| Material | Galvanised or stainless steel |
| Mounting | Floor bolted |
| Drain | Floor drain required |
Indicative values for this product class. Final specifications are confirmed on the quotation and in the calibration documents supplied with the instrument.
Applications
- Bulk chemical handling
- Process and plant areas
- Solvent transfer points
- Industrial laboratories
Key features
- Floor-mounted column, 2000–2400 mm high
- Overhead head covering 500–900 mm
- Flow 75–115 L/min, stay-open valve
- Pull rod or chain activation
- Galvanised or stainless steel
- Bolted base for stability
Frequently asked questions about Floor-Mounted Drench Shower
Where eye exposure is not a credible hazard, such as bulk handling of non-splashing liquids. If eye contact is possible, a separate eyewash within 10 seconds is still required.
Between 2000 and 2400 mm above the floor per ANSI/ISEA Z358.1, so a standing person is fully covered. Too high reduces coverage, too low restricts movement.
A drench shower produces thrust as water is released, and a movable column could topple or shift. Bolting the base and stabilising the column keeps the unit usable under full flow.
Within 10 seconds' travel of the hazard, about 15–20 m, on the same level and along an unobstructed path. The hazard and shower should not be separated by a door the casualty must open.
Because very cold water can cause shock and discourage a casualty from remaining for the full 15 minutes. ANSI/ISEA Z358.1 specifies tepid water, roughly 16–38 °C, for effective decontamination.
Activate weekly to flush the line and confirm the valve opens and stays open, and inspect annually for flow, temperature, spray pattern and height. Record both checks for audit and insurance.